Question 6 of 6 Intermediate

Happy with your answers?

Submit your current answers and get the final test result.

Submit

Test results

Congratulations. You have passed the test and completed the 5 - High efficiency hydronic systems

Achieved badges:

Continue training Go to MyECADEMY

Sorry. You did not pass the 5 - High efficiency hydronic systems test this time

Correct
Q: Why is a mixing loop the best way to control a radiant system?
A: Because flow rate and temperature can be adjusted according to the desired performance of the radiant surface
Correct
Q: What is the difference between sensible cooling and latent cooling?
A: Sensible cooling involves reduction in temperature while latent cooling involves removal of humidity from the air
Correct
Q: When is zoning an advantage?
A: When a building has different requirements to temperature or when the internal load from occupants is different.
Correct
Q: What influence does the introduction of radiant cooling systems have on other building services?
A: Air volumes, air handlers and air ducts can be reduced in size because radiant cooling systems take care of the sensible heat loads and a dedicated outdoor air systems can be introduced (DOAS).
Correct
Q: The indoor climate in a building with hydronic cooling is better than in a building with a forced air system. Why?
A: Because the use of hydronic systems for removing sensible heat loads means that less air is needed, which results in lower air velocities, less draft, and less noise.
Correct
Q: The heat energy distribution costs of hydronic systems are about 1/10 of the cost of a forced air system. How come?
A: Because forced air systems need much more air volumes to transport the same amount of energy than is the case with water.