Question 1 of 6 Intermediate

1 With a single dedicated pump for each terminal unit, which control mode is used?

Question 3 of 6 Intermediate

3 Why is there in most cases no bypass flow with a distributed pumping system?

Question 5 of 6 Intermediate

5 Pump energy savings in a distributed pumping system are around:

Question 6 of 6 Intermediate

6 How much flow is required to achieve almost 80 % of the capacity?

Question 6 of 6 Intermediate

Happy with your answers?

Submit your current answers and get the final test result.

Submit

Test results

Congratulations. You have passed the test and completed the 69 - The Grundfos Distributed Pumping Course

Achieved badges:

Continue training Go to MyECADEMY

Sorry. You did not pass the 69 - The Grundfos Distributed Pumping Course test this time

Correct
Q: With a single dedicated pump for each terminal unit, which control mode is used?
A: Constant temperature
Correct
Q: Why must low-pressure non-return valves be installed for each cooling loop with AHU’s?
A: To avoid backflow in case the AHU unit is out of operation
Correct
Q: Why is there in most cases no bypass flow with a distributed pumping system?
A: Because primary pumps try to match primary flow and secondary flow
Correct
Q: How does the MPC controller protect chillers from freezing?
A: By ensuring minimum flow over the active chille
Correct
Q: Pump energy savings in a distributed pumping system are around:
A: 54%
Correct
Q: How much flow is required to achieve almost 80 % of the capacity?
A: 50%